RAUCELL STEAM HEAT
EXCHANGERS; SERIAL–S
In an example below the pressure of the steam is 3 bars and the
temperature is 134 Cº.
Tempereatures of the water to be heated up are 10 - 55 Cº. The pressure loss of
the water is 50 kPa.
The diameter of the heat exchanger is 240 mm.
|
Type |
Heating Effect |
Water Flow |
Steam Consumption
|
Measures |
Weight |
| |
kW |
m3/h |
kg/h |
Φ/S |
kg |
| 240-45-9S |
198 |
3,8 |
329 |
240/52 |
15 |
| 240-45-15S |
314 |
6,0 |
522 |
240/63 |
17 |
| 240-45-23S |
471 |
9,0 |
782 |
240/80 |
19 |
| 240-45-35S |
706 |
13,5 |
1173 |
240/106 |
23 |
| 240-45-51S |
1020 |
19,5 |
1694 |
240/142 |
27 |
| 240-45-81S |
1606 |
30,7 |
2668 |
240/207 |
33 |
| 240-45-105S |
2082 |
39,8 |
3459 |
240/260 |
41 |
| 240-45-135S |
2669 |
51,0 |
4434 |
240/328 |
48 |
| 240-45-151S |
2983 |
57,0 |
4956 |
240/365 |
53 |
Φ = diameter
(mm)
S = thickness of the package (mm)
Note! In applications of heating up the water by steam, the care of
the right timely and slowly way of working of the steam valve shall be taken
care of in order to avoid the corrosion of cloride salts at excessive high
temperatures. To promote that purpose, it is useful to arrange continous flow of
the water through the heat exchanger.
In excessive conditions the better corrosion sustaining material than AISI316L
can be chosen.
See also
The Use and Servicing of RauCell Plate Heat Exchanger.